E6582062
9-3
9. Measures to satisfy standards
3
9
(2)
Examples of measures to comply with EMC Directive
The following are measures to comply with the EMC Directive when you use 480V class
products of VF-AS3 by installing it in other machines and systems.
• Examples of general measures
• When adding an EMC filter for further reduction of noise
• Measures for operation with external signals
The following are general EMC measures explained concretely.
VFAS3-4110KPC
2.5
-
150
VFAS3-4132KPC
2.5
-
150
VFAS3-4160KPC
2.5
-
50
VFAS3-4200KPC
2.5
-
50
VFAS3-4220KPC
2.5
-
50
VFAS3-4280KPC
2.5
-
50
Inverter type
Carrier
frequency
<F300>
Conducted noise
IEC61800-3 category C2
(EN55011 classB Group1)
Conducted noise
IEC61800-3 category C3
(EN55011 classB Group1)
Length of motor connecting cable
Length of motor connecting cable
(kHz)
(m)
(m)
Power supply wiring
(No shielded grounding needed)
[R/L1], [S/L2], [T/L3]
Motor wiring
(Shielded grounding needed)
[U/T1], [V/T2], [W/T3]
When the shielded wires need grounding,
modify before installing as shown in the
figure below.
Peel off the outer sheath of the cable
and fix the shielded part with a clamp.
Cable
Screws (x2)
Clamp
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...