E6582062
11-43
11. Table of parameters
1
3
9
10
11
F810
0810
Communication
frequency point
select
0: Disabled
1: RS485 (1)
2: RS485 (2)
3: Communication
option
4: Embedded Ethernet
-
-
0
Y
F811
0811
Communication
point 1 input value
0 - 100
%
0
Y
F812
0812
Communication
point 1 frequency
0.0 - FH
Hz
0.0
Y
F813
0813
Communication
point 2 input value
0 - 100
%
100
Y
F814
0814
Communication
point 2 frequency
0.0 - FH
Hz
50.0/
60.0
*2
Y
F820
0820
RS485 (2) baud
rate
0: 9600 bps
1: 19200 bps
2: 38400 bps
3: -
-
-
1
Y
F821
0821
RS485 (2) parity
0: Disabled
1: Even parity
2: Odd parity
-
-
1
Y
F823
0823
RS485 (2) time-out
time
0.0: Disabled
0.1 - 100.0
s
0.0
Y
F824
0824
RS485 (2) time-out
operation
1: Continue running
2, 3: -
4: Trip
5: -
6: Trip after deceleration
stop
-
-
1
Y
F825
0825
RS485 (2)
transmission wait
time
0.00 - 2.00
s
0.00
Y
F826
0826
RS485 (2) inverter
to inverter
communication
0: Follower (0Hz
command when
Leader fails)
1: Follower (continue
running when Leader
fails)
2: Follower (emergency
off when Leader fails)
3: Leader (transmit
frequency command)
4: Leader (transmit
output frequency
signal)
5: Leader (transmit
torque command)
6: Leader (transmit
output torque
command)
-
-
0
Y
F827
0827
RS485 (2) protocol
0: TOSHIBA
1: MODBUS
-
-
0
Y
Title
Communication
No.
Parameter name
Adjustment range
Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...