E6582062
10. Selection and installation of peripheral devices
10-4
9
10
According to the table [10. 2. 1], select an appropriate wiring device depending on the voltage class and
capacity of the inverter.
10. 2. 1 Selection table of a wiring device
Select a wiring device depending on the inverter type and input current in the table next.
■
Wiring devices for HD rating
10. 2 Selection of a wiring device
Voltage
class
Applicable
motor (kW)
Inverter type-form
Input current (A)
Rated current (A)
Molded-case circuit
breaker (MCCB)
Earth leakage circuit
breaker (ELCB)
Magnetic contactor
(MC)
3-phase
240 V
0.4
VFAS3-
2004P
1.7
3
20
0.75
2007P
3.3
5
20
1.5
2015P
6.0
10
20
2.2
2022P
9.0
15
20
4.0
2037P
15.1
20
20
5.5
2055P
20.1
30
32
7.5
2075P
27.3
40
32
11
2110P
40.0
50
50
15
2150P
53.2
75
60
18.5
2185P
64.8
100
80
22
2220P
78.3
100
80
30
2300P
104.7
150
150
37
2370P
128.4
175
200
45
2450P
157.6
200
260
55
2550P
189.0
250
260