11. Table of parameters
1
3
9
10
11
F495
0495
Over modulation
ratio
90 - 120
%
104
N
F498
0498
Parameter for
manufacturer
-
-
-
-
-
-
F499
0499
Parameter for
manufacturer
-
-
-
-
-
-
F500
0500
Acceleration time 2
0.0 - 6000 (600.0)
s
*1
Y
F501
0501
Deceleration time 2 0.0 - 6000 (600.0)
s
*1
Y
F502
0502
Acc/Dec pattern 1
0: Linear
1: S-Pattern 1
2: S-Pattern 2
-
-
0
Y
F503
0503
Acc/Dec pattern 2
0: Linear
1: S-Pattern 1
2: S-Pattern 2
-
-
0
Y
F504
0504
Panel Acc/Dec
select
1: Acc/Dec 1
2: Acc/Dec 2
3: Acc/Dec 3
4: Acc/Dec 4
-
-
1
Y
F505
0505
Acc/Dec switching
frequency 1
0.0: Disabled
0.1 - UL
Hz
0.0
Y
F506
0506
S-Pattern range at
Acc start
0 - 50
%
10
Y
F507
0507
S-Pattern range at
Acc completion
0 - 50
%
10
Y
F508
0508
S-Pattern range at
Dec completion
0 - 50
%
10
Y
F509
0509
S-Pattern range at
Dec start
0 - 50
%
10
Y
F510
0510
Acceleration time 3
0.0 - 6000 (600.0)
s
*1
Y
F511
0511
Deceleration time 3 0.0 - 6000 (600.0)
s
*1
Y
F512
0512
Acc/Dec pattern 3
0: Linear
1: S-Pattern 1
2: S-Pattern 2
-
-
0
Y
F513
0513
Acc/Dec switching
frequency 2
0.0: Disabled
0.1 - UL
Hz
0.0
Y
F514
0514
Acceleration time 4
0.0 - 6000 (600.0)
s
*1
Y
F515
0515
Deceleration time 4 0.0 - 6000 (600.0)
s
*1
Y
F516
0516
Acc/Dec pattern 4
0: Linear
1: S-Pattern 1
2: S-Pattern 2
-
-
0
Y
F517
0517
Acc/Dec switching
frequency 3
0.0: Disabled
0.1 - UL
Hz
0.0
Y
F519
0519
Unit of Acc/Dec
time
0: -
1: 0.01 s unit (0 after
execution)
2: 0.1 s unit (0 after
execution)
-
-
0
N
Title
Communication
No.
Parameter name
Adjustment range
Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...