5. [Fundamental operation] How to use parameters
3
4
5
9
Set <F631: Inverter overload detection> to "1: Temperature estimation".
• If the inverter overload trip "OL1" occurs, you can clear it by decreasing the value of <F601: Stall
prevention level 1> or setting <ACC: Acceleration time 1> or <dEC: Deceleration time 1> to a
longer value.
• To protect the inverter unit, you cannot turn off inverter overload detection.
0: 150%-60s (HD rating) or 0: 120
%
-60s (ND rating)
The inverter is protected with the uniform overload curve of 150%-60s (120%-60s for ND rating),
regardless of temperature.
1: Temperature estimation
Estimate inverter internal temperature rise and automatically adjust overload protection
characteristics (the diagonally shaded area in the following figure).
• When the output frequency is 0.1 Hz or less, or when the output current is 150% or more, the
overload trip "OL1" or overcurrent trips "OC1 through OC3" may occur in shorter time to protect
the inverter.
Title
Parameter name
Adjustment range
Default setting
F631
Inverter overload
detection
HD
0: 150%-60s
1: Temperature estimation
ND
0: 120%-60s
1: Temperature estimation
10
Inverter overload time(s)
Monitored output current (%)
60
0
110
Ჟ
150
Ჟ
105
%
(ND)
120
Ჟ
(ND)
Inverter overload protection characteristics
100%: Inverter rated output current
Current (%)
Inverter overload time (s)
(Outline data)
111
2400
120
240
130
120
140
80
150
60
165
2
200
0.5
60
0
110
Ჟ
150
Ჟ
Inverter overload time (s)
Inverter overload protection characteristics
Monitored output current (%)
100%: Inverter rated output current
<F631>=0
105
%
(ND)
120
Ჟ
(ND)
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...