E6582062
6-23
6. [Advanced] How to use parameters
3
4
6
9
■
Setting method
Set a frequency command for an analog input amount at two points.
For the corresponding parameters of each terminal and the setting method, refer to the following.
As default setting, the range between the minimum and maximum input amounts is set to 0 to 50.0/
60.0 Hz for main analog signal of the terminals. For example, the terminal [RR] is set to 0 to 50.0/
60.0 Hz at 0-10 V.
• For the terminal [RX], select the voltage for <F107: Terminal RX input voltage select>.
• For the terminal [AI4], select the analog signal for <F148: Terminal AI4 input select>. For the
terminal [AI5], select the analog signal for <F149: Terminal AI5 input select>. The terminals [AI4]
and [AI5] are optional.
• If noise disturbs stable operation, increase the value for <F209: Analog input filter>. Doing so
eliminates the noise of the frequency setting circuit.
• Do not set the same value for point 1 and point 2. Failure to do so displays "Err1".
For details on the analog signal setting, refer to [7. 3].
1) For setting the voltage input of 0-10 V (terminals [RR]), refer to the following
figure.
2) For setting current input of 4-20 mA (terminal [II]), refer to the following figure.
Output frequency (Hz)
Voltage signal (%)
50/60(Hz)
0(Hz)
100%
(10V)
0%
(0V)
Point 2
Point 1
<F203>
<F201>
<F202>
<F204>
Output frequency (Hz)
Voltage signal (%)
50/60(Hz)
0(Hz)
100%
(10V)
0%
(0mA)
20%
(4mA)
Point 2
Point 1
<F218>
<F216>
<F217>
<F219>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...