E6582062
6. [Advanced] How to use parameters
6-46
4
4
6
9
<F270: Jump frequency 1>
<F271: Jump frequency 1 band>
<F272: Jump frequency 2>
<F273: Jump frequency 2 band>
<F274: Jump frequency 3>
<F275: Jump frequency 3 band>
■
Function
When you want to avoid resonance caused by the natural frequency of the mechanical system to
run the inverter, the resonant frequency can be jumped.
This characteristic has hysteresis given to the jump frequency.
■
Parameter setting
■
Setting method
You can set three jump frequencies. To do that, avoid the overlap of the adjustment range of each
jump frequency.
The frequency does not jump during acceleration or deceleration.
6. 11 Jumping the frequency to avoid the
resonant frequency
Title
Parameter name
Adjustment range
Unit
Default setting
F270
Jump frequency 1
0.0 - FH
Hz
0.0
F271
Jump frequency 1 band
0.0 - 30.0
Hz
0.0
F272
Jump frequency 2
0.0 - FH
Hz
0.0
F273
Jump frequency 2 band
0.0 - 30.0
Hz
0.0
F274
Jump frequency 3
0.0 - FH
Hz
0.0
F275
Jump frequency 3 band
0.0 - 30.0
Hz
0.0
0.0Hz
STOP
13:12
F270 : Jump frequency 1
Min: 0.0
Max: 80.0
X1000
X100
X10
X1
0.0
Hz
Output frequency (Hz)
<F270: Jump frequency 1>
0
Frequency setting signal
<F271: Jump frequency 1 band>
<F273: Jump frequency 2 band>
<F275: Jump frequency 3 band>
<F272: Jump frequency 2>
<F274: Jump frequency 3>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...