6. [Advanced] How to use parameters
3
4
6
9
<F229: AI5 point 1 frequency>
<F230: AI5 point 2 input value>
<F231: AI5 point 2 frequency>
<F810: Communication frequency point select>
<F811: Communication point 1 input value>
<F812: Communication point 1 frequency>
<F813: Communication point 2 input value>
<F814: Communication point 2 frequency>
■
Function
These parameters set the output frequencies for the frequency commands of the analog signals.
You can use the following terminals. The terminals [AI4] and [AI5] are optional.
Voltage input (0 to 10 V)
: terminals [RR], [RX], [AI4], and [AI5]
Voltage input (-10 to +10 V) : terminals [RX], [AI4], and [AI5]
Curret input (4 to 20 mA)
: terminals [II], [AI4], and [AI5]
■
Parameter setting
Title
Parameter name
Adjustment range
Unit
Default setting
F107
Terminal RX input
voltage select
0: 0 to +10 V
1: -10 to +10 V
-
0
F108
Terminal RR input select
1: Voltage input (0-10 V)
2: -
3: -
4: PTC input
5: PT100 (2-wire) input
6: -
7: PT1000 (2-wire) input
8: -
9: KTY84 input
-
1
F148
Terminal AI4 input select
1: Voltage input (0-10 V)
2: Voltage input (-10 to +10 V)
3: Current input (0-20 mA)
4: PTC input
5: PT100 (2-wire) input
6: PT100 (3-wire) input
7: PT1000 (2-wire) input
8: PT1000 (3-wire) input
9: KTY84 input
-
1
F149
Terminal AI5 input select
1
F201
RR point 1 input value
0-100
%
0
F202
RR point 1 frequency
0.0-590.0
Hz
0.0
F203
RR point 2 input value
0-100
%
100
F204
RR point 2 frequency
0.0-590.0
Hz
50.0/60.0
*1
F205
RR point 1 rate
0-250
%
0
F206
RR point 2 rate
0-250
%
100
F209
Analog input filter
1: Disabled
2-1000
ms
1
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...