E6582062
5-13
5. [Fundamental operation] How to use parameters
3
4
5
9
■
Guideline for the setting
The criteria of acceleration time and deceleration time is the value of <FH: Maximum frequency>.
Note that it is not the value of <UL: Upper limit frequency>.
You can use <F519: Unit of Acc/Dec time> to switch the unit of setting time between 0.1s and 0.01s.
With acceleration/deceleration time set to 0.0 second, the unit of 0.05 second is used internally for
<F519> is "2: 0.1s unit" (default setting), and the unit of 0.01 second for <F519> is "1: 0.01s unit".
Memo
• When you set a time shorter than the optimum acceleration/deceleration time determined by
the load condition, the stall prevention action may cause the acceleration/deceleration time to
be longer than the setting value.
• If you set a further shorter acceleration/deceleration time, the inverter may stop due to an
overcurrent trip or overvoltage trip for protection. For details, refer to "Chapter 13".
• The stop methods of the motor are the deceleration stop by <dEC: Deceleration time 1> or the
coast stop. For details, refer to [6. 3. 1].
• You can set four types of options for each acceleration and deceleration time. For Acceleration
time 2 through 4 and Deceleration time 2 through 4, refer to [6. 27. 2].
Output frequency (Hz)
Time (s)
0
<FH>
<ACC>
<dEC>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...