E6582062
13. Trip information and measures
13-10
4
4
8
9
13
■
Pre-alarm information
■
Message information
PrA
STO activated
1) Open state between [STOA]/[STOB] and
[PLC] terminal.
2) 24V output terminal [PLC]/[P24] overload.
3) SW1 is set on "PLC" position and an
external power is not supplied.
1) Short circuit [STOA] - [STOB] - [PLC]. (By
default, short circuit is done with a shorting
bar).
2) Check 24V load.
3) Check SW1 position and external power
supply.
t
Communication
alarm
(RS485, option)
Condition very close to the communication
time out trip.
Perform the same measures with
communication time out "Err5" and "Err8".
tUn1
Brake learning error 1) The load is heavy.
2) Parameter setting is improper.
3) Braking operation is abnormal.
1) Perform learning with no load or light load
in approx. 3 % or less rating.
2) Set the motor parameters and learning
related parameters in advance.
3) Check the brake.
tUn3
Light-load high-
speed learning error
Setting of the motor parameter is improper.
Set the motor parameters according to the
motor.
Pre-alarm
display
English
Detection factor
Measures
C
Overcurrent pre-
alarm
Condition close to the overcurrent trip.
Perform the same measures with overcurrent
"OC1", "OC2", and "OC3".
H
Overheat pre-alarm Condition close to the overheat trip.
Perform the same measures with overheat
"OH".
L
Motor overload pre-
alarm
Condition close to the overload trip.
Perform the same measures with overload
"OL1", "OL2", and "OL3".
P
Overvoltage pre-
alarm
Condition close to the overvoltage trip.
Perform the same measures with overvoltage
"OP1", "OP2", and "OP3".
Message
display
English
Description
Remarks
A-01
V/f 5-point setting
error 1
When <Pt:V/f Pattern> = "7: V/f 5-point
setting", two or more from <vL>, <F190>,
<F192>, <F194>, <F196> and <F198> are
set to the same value other than 0.0 Hz.
Set different value on each parameter.
A-02
V/f 5-point setting
error 2
Inclination of V/f is large.
• Set V/f 5-point and <vLv>/<vL> for the V/f
inclination to be gentle.
• Increase the value of <VL>, or decrease
the value of <VLV>.
A-05
Base frequency
setting error
Tries to run in frequency over 10 times of the
base frequency.
• Check that the base frequency setting is
correct. <vL: Base frequency 1>, etc.
• Operate in frequency within 10 times of the
base frequency.
ASIA
Setting for Asia
Setting for Asia is selected in the setup
menu.
-
Atn
During auto tuning
Auto-tuning in progress.
A message that indicates auto-tuning in
progress. No problem if the message
disappears after several seconds.
Alarm
display
English
Detection factor
Measures
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...