E6582062
13-3
13. Trip information and measures
I
II
III
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
E-29
003D
Control power
option failure *
1) Failure on the control power supply
option.
2) The setting of <F647: Control power
option failure detection> is improper.
1) When input voltage of the control power
supply is normal and the voltage
between terminals [+SU]-[CC] is under
20 Vdc, it is a failure in the control
power supply option.
Contact your Toshiba distributor.
2) When the control power supply option is
not used, set <F647> = "0".
E-31
003F
Rush current
suppression
relay fault
1) Fault on the rush current suppression
relay.
2) The power was turned ON/OFF
frequently.
1) Fault in internal inverter.
Contact your Toshiba distributor.
2) Instead of turning ON/OFF with the
power supply, turn ON/OFF with a run
command.
E-32
0040
PTC failure
1) PTC protection for the motor became
enabled.
2) Failure in the PTC circuit.
1) Check the motor and PTC.
2) Failure in internal inverter.
Contact your Toshiba distributor.
E-37
0045
Servo lock
error
1) The lock up torque or more external
load is applied to the motor.
2) Setting of motor parameters is
improper.
1) Reduce the load to apply the servo
lock.
2) Set the motor parameters according to
the motor characteristic, and perform
auto-tuning.
<vL: Base frequency 1>,
<vLv: Base frequency voltage>,
<F405: Motor rated capacity>,
<F415: Motor rated current>,
<F417: Motor rated speed>,
<F400: Offline auto-tuning>, etc.
E-38
0046
Communicati
on time-out of
A6 Brake Unit
1) The wire linked VF-AS3 to A6 Brake
Unit is disconnected.
2) The A6 Brake Unit is failed.
1) Check the wire linked VF-AS3 to A6
Brake Unit.
2) Turn off the power and then turn it on
again.
If the fault occurs again, contact your
Toshiba distributor.
E-39
0047
PM control
error
During auto-tuning or initial position, the
motor current became very high.
Measure inductance with a LCR meter,
etc., and set to the parameter directly.
E-42
004A
Cooling fan
fault
The cooling fan failed.
The cooling fan needs to be replaced.
Contact your Toshiba distributor.
E-43
004B
Communicati
on time-out
(embedded
Ethernet)
Embedded Ethernet communication timed
out.
Check the Ethernet communication
equipment and wiring.
E-44
004C
Battery of
panel failure
Calendar function is activated, and under
one of these cases.
1) A battery is not in.
2) The battery level is low.
1) Put a battery.
2) Replace the battery.
E-45
004D
GD2 auto-
tuning error
• The value of F459 is not fixed.
• Estimated value of F459 is out of
parameter range.
1) Modify the value of F481, F482 and do
the tuning again.
2) Modify F480 to 0, and set the
appropriate value of F459 manually.
E-48
0050
A6 Brake Unit
internal fault
An internal error occurred in A6 Brake
Unit.
Turn off the power and then turn it on
again.
If the fault occurs again, contact your
Toshiba distributor.
E-99
0058
Trip for test *
Trip for test occurred.
Reset if no problem is found.
*Enable/Disable can be selected for trip with a parameter.
Trip
display
Failure
code
Trip name
Detection factor
Measures
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...