6. [Advanced] How to use parameters
3
4
6
9
■
Guideline for the setting
The override functions calculate the frequency command value by means of the following
expression:
• Frequency command value × (1+<F661> Input (%)/100) + <F660> Input (Hz)
<F661> is limited to -100 to +100
However, when the setting value of <F661: Override multiplying input select> is *1 in the table, use
the following expression.
• Frequency command value × (<F661> Input (%)/100) + <F660> Input (Hz)
<F661> is not limited
■
Additive override
An input override frequency is added to the frequency command value externally.
Example 1: <F660>= "3: Terminal II", <F661>= "0: Disabled"
Output frequency = Reference fre Override (terminal [II] input (Hz))
Example 2: <F660>= "1: Terminal RR", <F661>= "0: Disabled"
Output frequency = Reference fre Override (terminal [RR] input (Hz))
■
Multiple override
An input override frequency is added to the frequency command value externally.
F729
Panel override
multiplication gain
-100 to +100
%
0
Title
Parameter name
Adjustment range
Unit
Default setting
Output frequency
Output frequency
Frequency after
override
Frequency after override
Fwd
Rev
Example 1: Terminal [RR]
(Reference frequency command)
Terminal
[II]
(override
input)
Example 2: Terminal [RX]
(Reference frequency command)
Terminal
[RR]
(override
input)
Override
([II] input)
Override
([II] input)
[RR] input
(Reference
frequency)
[RX] input
(Reference
frequency)
0
10V
10V
0
-10V
<FH>
<FH>
<FH>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...