E6582062
11-3
11. Table of parameters
1
3
9
10
11
FMOd
0004
Frequency
command
select 1
0: -
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5: Terminal AI5 (option)
6 - 9: -
10: Touch wheel 1 (power off
or press OK to save)
11: Touch wheel 2 (press OK
to save)
12: Sr0
13,14: -
15: Terminal Up/Down
frequency
16: Pulse train
17: High resolution pulse
train (option)
18,19: -
20: Embedded Ethernet
21: RS485 communication
(connector 1)
22: RS485 communication
(connector 2)
23: Communication option
-
-
1
N
[4. 3. 1]
[4. 4. 1]
[5. 2. 1]
[5. 4. 1]
[7. 3. 2]
[7. 3. 3]
[7. 3. 4]
Pt
0015
V/f Pattern
0: V/f constant
1: Variable torque
2: Automatic torque boost
3: Vector control 1
4: Energy savings
5: Dynamic energy savings
(for fan and pump)
6: PM motor control
7: V/f 5-point setting
8: -
9: Vector control 2
(speed / torque)
10: PG feedback control
11: PG feedback vector
control (speed / torque)
12: -
-
-
0
N
vb
0016
Manual
torque boost
1
0.00 - 30.00
%
*1
Y
[5. 3. 6]
vL
0014
Base
frequency 1
15.0 - 590.0
Hz
50.0 /
60.0 *2
Y
[5. 2. 2]
vLv
0409
Base
frequency
voltage 1
240V class: 50-330V
480V class: 50-660V
V
*2
Y
FH
0011
Maximum
frequency
30.0 - 590.0
Hz
*2
N
UL
0012
Upper limit
frequency
0.0 - FH
Hz
50.0 /
60.0 *2
Y
[5. 2. 3]
LL
0013
Lower limit
frequency
0.0 - UL
Hz
0.0
Y
ACC
0009
Acceleration
time 1
0.0 - 6000 (600.0)
s
*1
Y
Title
Communication
No.
Parameter
name
Adjustment range
Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...