E6582062
7. Operating using external signals
7-18
4
4
4
7
9
7. 3. 3
Inputting the frequency commands by current
(4 - 20 mAdc)
Input the current signal of 4(0) - 20 mAdc between the terminals [II]-[CC].
■
Setting example
The following shows an example of how to externally input the run commands to the digital input
terminals with a current input of 4 - 20 mAdc.
The frequency shall be 0 Hz for the minimum input of 4 mA, and 60 Hz for the maximum input of 20
mA.
• <CMOd: Run command select> = "0: Terminal"
• <FMOd: Frequency command select 1> = "3: Terminal II"
• <F216: II point 1 input value> = "20" (%)
(default setting)
• <F217: II point 1 frequency> = "0" (Hz)
(default setting)
• <F218: II point 2 input value> = "100" (%)
(default setting)
• <F219: II point 2 frequency> = "60" (Hz)
(default setting)
For the characteristics of input currents and output frequencies, set at two points of <F216> and
<F217>, and <F218> and <F219>. The reference for 100% of the input value is 20mA.
(In case of sink logic)
R/L1
S/L2
T/L3
FLA
FLB
FLC
U/T1
V/T2
W/T3
F
Fwd run
4(0) to 20 mAdc
Rev run
R
I I
CC
MCCB
or
ELCB
Inverter
Motor
M
Output frequency (Hz)
Point 2
Point 1
Voltage signal (%)
100%
(20mA)
0%
(0mA)
20%
(4mA)
Power
supply
<F219>
<F217>
<F216>
<F218>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...