E6582062
5-7
5. [Fundamental operation] How to use parameters
3
4
5
9
5. 2. 2
Setting rated frequency and rated voltage of motor
<vL: Base frequency 1>
<vLv: Base frequency voltage 1>
■
Function
These parameters are used to set the rated frequency and rated voltage of the motor according to
machinery. They are important parameters to decide the control range of the inverter.
■
Parameter setting
■
Reference of setting
Set the rated frequency (50 Hz, 60 Hz, etc.) and rated voltage (200 V, 220 V, etc.) of the motor
according to the specifications of machinery.
The inverter is controlled based on the rating of the motor specified with these parameters.
Title
Parameter name
Adjustment range
Unit
Default setting
vL
Base frequency 1
15.0 - 590.0
Hz
50.0/60.0
*1
*1 Depending on the setup menu. Refer to [5. 3. 10].
The value of <VL> should be equal or smaller than that of <FH>.
vLv
Base frequency
voltage 1
240V class: 50-330
480V class: 50-660
V
*1
0.0Hz
STOP
15:25
Min: 15.0
Max: 590.0
X1000
X100
X10
X1
Hz
vL :Base frequency 1
60.0
Basic parameter
0.0Hz
STOP
15:26
vLv :Base frequency voltage 1
Min: 50
Max: 660
X1000
X100
X10
V
400
X1
Basic parameter
Output frequency (Hz)
Output voltage (V)
0
<vLv: Base
frequency voltage 1>
<vL: Base frequency 1>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...