E6582062
5. [Fundamental operation] How to use parameters
5-12
4
5
9
5. 2. 4
Setting acceleration/deceleration time
<ACC: Acceleration time 1>
<dEC: Deceleration time 1>
■
Function
Set a time for acceleration and deceleration.
In <ACC: Acceleration time 1>, set a time before the output frequency of the inverter reaches the
value of <FH: Maximum frequency> from 0.0 Hz.
In <dEC: Deceleration time 1>, set a time before the output frequency of the inverter decreases to
0.0 Hz from the value of <FH: Maximum frequency>.
Unit for a setting time is selected with <F519: Unit of Acc/Dec time>.
■
Parameter setting
Title
Parameter name
Adjustment range
Unit
Default setting
ACC
Acceleration time 1
0.0 - 6000 (600.0)
s
*1
*1 The default is 10.0/30.0/60.0 (s) depending on the capacity. Refer to [11. 6].
dEC
Deceleration time 1
0.0 - 6000 (600.0)
s
Title
Parameter name
Adjustment range
Default
setting
F519
Unit of Acc/Dec time
0: -
1: 0.01s unit (0 after execution)
2: 0.1s unit (0 after execution)
0
0.0Hz
STOP
15:09
ACC :Acceleration time 1
Min: 0.0
Max: 6000.0
X1000
X100
X10
X1
s
10.0
Basic parameter
Easy mode
Basic parameter
Easy mode
0.0Hz
STOP
15:10
dEC :Deceleration time 1
Min: 0.0
Max: 6000.0
X1000
X100
X10
X1
s
10.0
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...