E6582062
5. [Fundamental operation] How to use parameters
5-56
4
5
9
3) Adjusting PID control gain level
Adjust the PID control gain level according to the set values, the feedback signals, and the
object to be controlled.
<F362: PID1 proportional gain>
This parameter adjusts the proportional gain level of PID control. A correction value proportional
to the particular deviation (the difference between the set value and the feedback value) is
obtained by multiplying this deviation by the parameter setting.
A larger P-gain adjustment value gives faster response. Too large an adjustment value,
however, results in an unstable event such as hunting.
<F363: PID1 integral gain>
This parameter adjusts the integral gain level of PID control. Any remaining deviations (residual
deviation offset) during proportional action are cleared to zero.
A larger I-gain adjustment value reduces residual deviations. Too large an adjustment value,
however, results in an unstable event such as hunting.
Memo
• PID control can be temporarily turned off with an external signal. Assign "36: PID control OFF"
to an input terminal.
• PID control should be OFF when very low speed drive is needed.
• If speed PID is selected, motor is possibly rotating forward and reverse. If you don't want to
rotate reverse, set <F311: Reverse inhibited> or select process PID (<F359>=1, or 11).
Title
Parameter name
Adjustment range
Unit
Default
setting
F362
PID1 proportional gain
0.01 - 100.0
-
0.30
F363
PID1 integral gain
0.01 - 100.0
s
-1
0.20
F366
PID1 differential gain
0.00 - 2.55
s
0.00
PID set value
Output frequency
Fast response
Large
Slow response
Time
Small
<F362>
<F362>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...