5. [Fundamental operation] How to use parameters
3
4
5
9
2) Setting contents of PID control
Set <F359: PID control 1> to "1: Process PID control".
Set <ACC: Acceleration time 1> and <dEC: Deceleration time 1> to the time that is suitable for
the system. Refer to [5. 2. 4].
To limit the setting values, set the following parameters.
• To limit the set value: <F367: PID1 set value upper-limit>, <F368: PID1 set value lower-limit >
• To limit the output frequency: <UL: Upper limit frequency>, <LL: Lower limit frequency>
Title
Parameter name
Adjustment range
Default
setting
F389
PID1 set value select
0: selected by FMOd/F207
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5: Terminal AI5 (option)
6 - 11: -
12: FPId
13, 14: -
15: Terminal Up/Down frequency
16: Pulse train
17: High resolution pulse train (option)
18, 19: -
20: Embedded Ethernet
21: RS485 communication (connector 1)
22: RS485 communication (connector 2)
23: Communication option
0
F360
PID1 feedback input
select
0: -
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5: Terminal AI5 (option)
6 - 16: -
17: High resolution pulse train (option)
0
Title
Parameter name
Adjustment range
Unit
Default
setting
F359
PID control 1
0: Disabled
1: Process PID control
2: Speed PID control
3: Easy positioning P control
4: Dancer control
5 - 10: -
11: Minus Process PID control
12: Minus Speed PID control
13: Minus Easy positioning P control
14: Minus Dancer control
0
F367
PID1 set value upper-
limit
0.0 - FH
Hz
50.0/60.0
F368
PID1 set value lower-limit
0.0 - F367
Hz
0.0
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...