E6582062
6. [Advanced] How to use parameters
6-186
4
4
6
9
F814
Communication point 2
frequency
0.0-FH
Hz
50.0/60.0
*4
F820
RS485 (2) baud rate
0: 9600 bps
1: 19200 bps
2: 38400 bps
1
F821
RS485 (2) parity
0: Disabled
1: Even parity
2: Odd parity
1
F823
RS485 (2) time-out time
0.0: Disabled
0.1 - 100.0
s
0.0
F824
RS485 (2) time-out
operation
1: Continue running
2, 3: -
4: Trip
5: -
6: Trip after Deceleration stop
0
F825
RS485 (2) transmission
wait time
0.00 - 2.00
s
0.00
F826
RS485 (2) inverter to
inverter communication
0: Follower (0Hz command when Leader
fails)
1: Follower (continue running when Leader
fails)
2: Follower (emergency off when Leader
fails)
3: Leader (transmit frequency command)
4: Leader (transmit output frequency signal)
5: Leader (transmit torque command)
6: Leader (transmit output torque command)
0
F827
RS485 (2) protocol
0: TOSHIBA
1: MODBUS
0
F828
RS485 (2) time-out
detection
0: Always
1: Run command and frequency command
by communication are enabled.
2: During run by communication
1
F829
RS485 (2) wiring type
0: 2-wire
1: 4-wire
0
F830
MODBUS continuous
address
0: Disabled
1: Enabled
0
F856
Motor pole number for
communication
1: 2 pole
2: 4 pole
3: 6 pole
4: 8 pole
5: 10 pole
6: 12 pole
7: 14 pole
8: 16 pole
2
F870
Block write data 1
0: Disabled
1: Communication command 1
2: Communication command 2
3: Frequency command
4: TB output
5: Analog output
6: Speed command by communication
0
F871
Block write data 2
0
Title
Parameter name
Adjustment range
Unit
Default setting
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...