E6582062
6-151
6. [Advanced] How to use parameters
3
4
6
9
6. 30. 21 Setting number of starting alarm and alarm
occurrence of the specified trip
<F648: Number of starting alarm>
<F658: Number of external equipment starting alarm>
<F664: Specified trip 1>
<F665: Specified trip 2>
<F666: Specified trip 3>
■
Function
This parameter counts the number of starting of the inverter, and when it reaches the value set by
<F648: Number of starting alarm>, it outputs the alarm and confirm it in [Monitor mode].
For number of external equipment starting alarm, you can outputs the alarm and confirm it in
[Monitor mode]. For number of starting for external equipment, the number of input to the input
terminal is counted.
Also, occurrence of the specified trip can be confirmed in [Monitor mode].
■
Parameter setting
■
Signal output of the number of starting alarm of the inverter
This parameter counts the number of starting of the inverter, and when it reaches the value set by
<F648: Number of starting alarm>, it outputs the alarm and confirm it in [Monitor mode].
Output alarm
Assign "162: Number of starting alarm" to the unused output terminal. For details, refer to [7. 2. 2].
[Monitor mode]
Set "100: Number of starting" to <F711: Monitor mode 1 display> through <F718: Monitor mode 8
display>. For details, refer to [8. 1. 1].
■
Signal output of the number of external equipment starting alarm
This parameter counts the number of starting of the external equipment, and when it reaches the
values set by <F658: Number of external equipment starting alarm>, it outputs the alarm and can be
confirmed in [Monitor mode].
For Number of starting for external equipment, a signal to the input terminal with the function of "114:
External equipment counter" is assigned is counted.
Output alarm
Title
Parameter name
Adjustment range
Unit
Default setting
F648
Number of starting alarm
0 - 999.0
x10,000 times
999.0
F658
Number of external
equipment starting alarm
0 - 999.0
x10,000 times
999.0
F664
Specified trip 1
0 - 1 00
Times
0
F665
Specified trip2
0 - 1 00
Times
0
F666
Specified trip3
0 - 1 00
Times
0
0.0Hz
STOP
14:06
F648 : Number of starting alarm
Min: 0.0
Max: 999.0
X1000
X100
X10
X1
0.0
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...