E6582062
6-147
6. [Advanced] How to use parameters
3
4
6
9
6. 30. 19 Motor PTC thermal protection setting
<F645: Terminal RRPTC trip>
<F646: PTC detection resistance>
<F108: Terminal RR input select>
<F148: Terminal AI4 input select>
<F149: Terminal AI5 input select>
<F637: Terminal AI4 PTC trip>
<F638: Terminal AI5 PTC trip>
■
Function
This function is set to protect the motor from overheating by using PTC, which is integrated in the
monitor.
You can trip the motor. The trip display is "E-32".
■
Parameter setting
■
PTC thermal protection using terminal [RR]
Connect PTC between terminals [RR]-[CC].
Set "4", "5", "7", and "9" with <F108: Terminal RR switching>.
In <F645: Terminal RR PTC trip>, when "0: Disabled" is selected, pre-alarm only, and when "1:
Enabled" is selected, pre-alarm and trip are enabled.
Title
Parameter name
Adjustment range
Unit
Default setting
F645
Terminal RR PTC trip
0: Disabled
1: Enabled
0
F646
PTC detection resistance
100 - 9999
Ω
3000
F656
PTC detection
temperature
0 - 200
°C
90
F108
Terminal RR input
1: Voltage input (0-10V)
2, 3: -
4: PTC input
5: PT100 (2-wire) input
6: -
7: PT100 (2-wire) input
8: -
9: KTY84 input
1
F148
Terminal AI4 input select
1: Voltage input (0-10 V)
2: Voltage input (-10 to +10 V)
3: Current input (0-20 mA)
4: PTC input
5: PT100 (2-wire) input
6: PT100 (3-wire) input
7: PT100 (2-wire) input
8: PT1000 (3-wire) input
9: KTY84 input
0
F149
Terminal AI5 input select
F637
Terminal AI4 PTC trip
0: Disabled
0
F638
Terminal AI5 PTC trip
1: Enabled
0.0Hz
STOP
14:04
F645 : Terminal RR PTC trip
0: Disabled
1: Enabled
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...