6. [Advanced] How to use parameters
3
4
6
9
6. 30. 14 Undervoltage trip setting
<F627: Undervoltage trip>
<F625: Undervoltage detection level>
<F628: Undervoltage detection time>
■
Function
This parameter sets the action when undervoltage of the power circuit is detected.
When undervoltage is detected, it displays "MOFF" and stops. Alarm can be output from the output
terminal.
If you want to trip, set by <F627: Undervoltage trip>. The trip display is "UP1".
■
Parameter setting
■
Detection level of undervoltage alarm "MOFF"
Exclude <F625: Undervoltage detection level> = "80: Auto"
The occurrence level of MOFF alarm is the setting value of <F625>. MOFF alarm will be cleared at
the setting value of <F629: Regenerative power ride-through level>.
When <F625: Undervoltage detection level> = "80: Auto"
Both occurrence level and clear level of MOFF alarm is followed by the level specified by the internal
setting.
■
Setting the <F627: Undervoltage trip>
0: Disabled
The inverter stops but does not trip. (Failure signal FL disabled)
1: Enabled
The inverter trips after undervoltage is detected for the period of time set by <F628: Undervoltage
detection time> or longer. The trip display is "UP1". (Failure FL enabled)
Title
Parameter name
Adjustment range
Unit
Default setting
F627
Undervoltage trip
0: Disabled
1: Enabled
0
F625
Undervoltage detection
level
50 - 79
80: Auto
%
80
*1
*1 100% reference of <F625> is 200 V (240V class), 400 V (480V class).
F628
Undervoltage detection
time
0.01 - 10.00
s
0.03
F629
Regenerative power ride-
through level
55 - 100
%
75
0.0Hz
STOP
14:01
F627 : Undervoltage trip
0: Disabled
1: Enabled
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...