E6582062
6-3
6. [Advanced] How to use parameters
3
4
6
9
6. 1. 2
Output a signal when reached to a frequency
command (output the Acc/Dec completed signal)
<F102: Reach signal detection band>
■
Function
When the output frequency becomes the frequency command ±<F102: Reach signal detection
band>, the Acc/Dec completed signal is output from the output terminal.
■
Parameter setting
■
Output terminal parameter setting
Acc/Dec completed signal is the default setting for output terminal [FP].
Title
Parameter name
Adjustment range
Unit
Default setting
F102
Reach signal detection
band
0.0-FH
Hz
2.5
Title
Parameter name
Adjustment range
Default setting
F130
Terminal FP function 1
0-255
*1
*1 For details on the output terminal functions, refer to [7. 2. 2].
6
0.0Hz
STOP
12:43
F102 : Reach signal detect band
Min: 0.0
Max: 80.0
X1000
X100
X10
X1
Hz
2.5
ON
OFF
Output frequency (Hz)
Time (s)
Frequency command value
Frequency command value +
Terminal [FP]
(Acc/Dec completed)
ON
OFF
Terminal [F]
(Fwd run)
0
Frequency command value -
<F102>
<F102>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...