Chapter 8: Using the Command Line Interface
492
Example 1 - Environmental Sensor Naming
The following command assigns the name "Cabinet humidity" to the
environmental sensor with the ID number 4.
config:#
externalsensor 4 name "Cabinet humidity"
Example 2 - Sensor Threshold Selection
The following command sets the environmental sensor #1 to use the
default thresholds, including the deassertion hysteresis and assertion
timeout, as its threshold settings.
config:#
externalsensor 1 useDefaultThresholds true
Configuring Environmental Sensors' Default Thresholds
You can set the default values of upper and lower thresholds,
deassertion hysteresis and assertion timeout on a sensor type basis,
including temperature, humidity, air pressure and air flow sensors. The
default thresholds automatically apply to all environmental sensors that
are newly detected or added.
A default threshold configuration command begins with
defaultThresholds.
You can configure various default threshold settings for the same sensor
type at a time by combining multiple commands. See
Multi-Command
Syntax
(on page 520).
Set the Default Upper Critical Threshold for a specific sensor
type:
config:#
defaultThresholds <sensor type> upperCritical <value>
Set the Default Upper Warning Threshold for a specific sensor
type:
config:#
defaultThresholds <sensor type> upperWarning <value>
Set the Default Lower Critical Threshold for a specific sensor
type:
config:#
defaultThresholds <sensor type> lowerCritical <value>
Set the Default Lower Warning Threshold for a specific sensor
type:
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...