Chapter 3: Initial Installation and Configuration
48
All internal sensors become "unavailable", including sensors of
inlets, outlets, and OCPs.
Exception: Only active energy data remains available.
Communications with relay/meter boards are lost. Therefore,
firmware upgrade may fail due to this reason.
Available data or operations on the PDU that enters the
power-sharing mode:
Change software settings, such as customizing names, modifying
network settings, configuring thresholds, and so on.
Note: Outlet switching is not available because all outlets lose
power.
Monitor the status of connected Raritan environmental sensor
packages, or configure/control their settings.
Operate the front panel display.
Exception: Operation of the front panel display is NOT available on a
PX3 with residual current monitoring because it assumes that there
is an RCM alarm when losing power supply from the inlet.
Events that occur when entering the power-sharing mode:
The 12V power supply sensor enters the fault state. See
+12V Power
Supply Sensor (for iX7
™
Only)
(on page 154).
Tip: You can set an event rule for sending a notification when this
sensor enters the fault state. See
Event Rules and Actions
(on page
The above event is logged in the internal event log. See
Default Log
Messages
(on page 278).
To find whether an iX7
™
has entered the power-sharing mode:
Check the state of its +12V power supply sensor.
Tip: For SNMP, the sensor type for this +12V power supply is
i1smpsStatus (46).
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...