Appendix L: Integration
698
Configuring Rack PDU Targets
KX III allows you to connect rack PDUs (power strips) to KX III ports.
KX III rack PDU configuration is done from the KX III Port Configuration
page.
Note: Raritan recommends no more than eight (8) rack PDUs (power
strips) be connected to a KX III at once since performance may be
affected.
Connecting a PX PDU
Raritan PX series rack PDUs (power strips) are connected to the
Dominion device using the D2CIM-PWR CIM.
To connect the rack PDU:
1.
Connect the male RJ-45 of the D2CIM-PWR to the following female
RJ-45 connector of the rack PDU.
PX1 series: RJ-45 "SERIAL" port
PX2 or PX3 series: RJ-45 "FEATURE" port
2.
Connect the female RJ-45 connector of the D2CIM-PWR to any of the
available female system port connectors on the KX III using a
straight through Cat5 cable.
3.
Attach an AC power cord to the target server and an available rack
PDU outlet.
4.
Connect the rack PDU to an AC power source.
5.
Power on the device.