Chapter 6: Using the Web Interface
206
Tip: You can also create event rules to notify you of the warning or
critical levels. See
Event Rules and Actions
(on page 272).
To view sensor alerts and LHX event log:
Remote alert acknowledgment is supported by the LHX-20 and LHX-40.
The SHX-30 does not support this feature.
1.
Locate the Alert States section.
2.
If any LHX sensors fail, they are indicated. Click Acknowledge to
acknowledge the sensor failure.
3.
To view the history of LHX events, click Show Event Log to go to the
Event Log page.
Operation time statistics:
This section indicates the accumulative operation hours of the LHX/SHX
device and its fans since the device is connected to the PX3 and turned
on.
Available time units in the statistics --
h: hour(s)
d: day(s)
Request maximum cooling:
Only SHX 30 supports this feature. See
SHX Request Maximum Cooling
(on page 206).
SHX Request Maximum Cooling
The PX3 allows you to remotely activate the Schroff SHX 30's maximum
cooling feature. Both LHX 20 and LHX 40 do not support remote
activation of maximum cooling.
The Request Maximum Cooling feature is available only after the PX3
detects SHX 30. For additional information on the SHX 30 maximum
cooling feature, see the SHX 30 documentation.
To perform maximum cooling:
Go to the SHX page, and click Request Maximum Cooling.
Then the SHX 30 enters into emergency cooling mode and runs at its
maximum cooling level of 100% in order to cool the device.
When maximum cooling is requested for an SHX 30, the message
"Maximum cooling requested" is displayed.
To stop maximum cooling:
Click Cancel Maximum Cooling.
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...