CEP 6506GU, 6506G 

Temporary branch power distribution unit 

 with Ground fault protection for personnel

 

 

 

Installation and Operating Instructions 

 
SPECIFICATION 
These installation and operation instructions 
apply to the following temporary power 
branch distribution system components. Do 
not discard these instructions, save for future 
Reference. 

PORATBLE POWER  

DISTRIBUTION UNITS 

All units are rated 50 amps, 125/250 VAC, 
Single Phase, 5 milliampere leakage current 
trip level. Downstream protection is not provided 
through the 50 amp outlet. The 20 amp, 120 volt 
outlets are individually  
protected by circuit breakers and GFCI 
circuit modules. 
 

Model 

Number 

20 Amp 

Receptacle 

6506GU 

U-Ground 

6506G 

Twist-Lock 

 

INTRODUCTION 
CEP temporary power distribution units equipped 
with GFCI products will protect you from 
electrocution hazards resulting from ground 
faults.  Ground faults are current leaks and can 
result in electric shock. Currents of only 60/1000 
of an ampere can be fatal. The GFCI protection 
provided by CEP temporary power distribution 
units significantly minimizes shock hazards. CEP 
temporary power distribution units, which are UL 
listed as Class A, Group I interrupters, respond 
to fault currents as low as 3-6 milliamperes, and 
will shut of the current within 1/40

th

 of a second. 

 

 

 

 
 

The temporary power distribution unit is 
designed to provide protection against electrical 
shock hazards due to line-to-ground faults. 
Although the GFCI Module does not eliminate 
the hazard of a shock, it does limit the duration 
of the shock to a period considered safe for 
normally healthy persons. 
GFCI Modules will provide protection against 
ground faults only. They will not protect against 
overloads or short circuits. There is no known 
device that will guard against the electrical shock 
hazard resulting from contact with both the “hot” 
and neutral wires of the electrical circuit. 
ELECTRICITY IS DANGEROUS. 
EVEN WHEN SAFETY DEVICES ARE 
PRESENT, HANDLE WITH CARE AND USE 
REASONABLE CAUTION. 
 
LET CAUTION PREVAIL 
The CEP temporary power distribution unit is 
designed to be used on a grounded electrical 
supply system. It will not operate when supplied 
from a power source which is not grounded.  
Over-current protection of the proper rating, 
according to the National Electric Code, Article 
240, must be used on the supply circuit feeding 
the temporary power distribution units. 
 
TEST PROCUDURE 
All Models 
Connect the temporary power distribution unit to 
an appropriate power source. 
CAUTION 

 

Power is immediately available at the 50 
amp outlet when the source is energized 
on all models. 

1.  Verify all circuit breakers are in the “on” 
position. 