Chapter 6: Using the Web Interface
196
Field
Description
Name
Name for this asset strip assembly.
Number of Rack
Units
Total of available tag ports on this asset strip
assembly, ranging between 8 and 64.
For the current generation of asset strips,
which show the suffix "G3" on its hardware
label, the PX3 automatically detects the
number of its tag ports (rack units), and you
cannot change this value.
For old "non-G3" asset strips, there is no
automatic detection for them so you must
manually adjust this value.
Numbering Mode
The rack unit numbering method in a
rack/cabinet.
Top-Down: The numbering starts from the
highest rack unit of a rack/cabinet.
Bottom-Up: The numbering starts from the
lowest rack unit of a rack/cabinet.
Numbering Offset The start number in the rack unit numbering.
For example, if this value is set to 3, then the
first number is 3, the second number is 4, and
so on.
Orientation
The asset strip's orientation by indicating the
location of its RJ-45 connector.
Top Connector: The RJ-45 connector is
located on the top.
Bottom Connector: The RJ-45 connector is
located on the bottom.
Asset strips can detect their strip orientation
and show it in this field.
You need to adjust this value only when your
asset strips are the oldest ones without tilt
sensors implemented.
Color with
connected tag
Click this field to determine the LED color
denoting the presence of an asset tag.
Default is green.
Color without
connected tag
Click this field to determine the LED color
denoting the absence of an asset tag.
Default is red.
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...