Chapter 8: Using the Command Line Interface
408
Option
Description
lastKnownState Restores all outlets to the previous status before
powering down the PX3 device when the PDU
powers up again.
Note: This feature does NOT take effect and cannot be configured on a
PX3 device after the outlet relay is set to the "Latching" mode. See
PX3
Latching Relay Behavior
(on page 150).
Setting the PDU-Defined Cycling Power-Off Period
This section applies to outlet-switching capable models only.
This command sets the power-off period of the power cycling operation
for all outlets.
config:#
pdu cyclingPowerOffPeriod <timing>
Variables:
<timing> is the time of the cycling power-off period in seconds,
which is an integer between 0 and 3600, or
pduDefined for following
the PDU-defined timing.
Setting the Inrush Guard Delay Time
This section applies to outlet-switching capable models only.
This command sets the inrush guard delay.
config:#
pdu inrushGuardDelay <timing>
Variables:
<timing> is a delay time between 100 and 100000 milliseconds.