Appendix F: PX3 Models with Residual Current Monitoring
598
6.
After completing the RCM self-test, the LCD display indicates the
RCM self-test result: passed or failed.
7.
Press
/
or
/
to return to the RCM information page.
8.
Do one of the following:
To return to the Main Menu, press
/
.
To perform RCM self-test for additional inlets, press
/
or
/
to select a different inlet and repeat the same steps.
RCM SNMP Operations
Make sure you have the correct version of SNMP MIB. The PX3 supports
the RCM feature as of firmware version 2.5.20. See
Downloading SNMP
MIB
(on page 360) for details.
RCM Trap
An
InletSensorStateChange trap is sent when the RCM state sensor
changes.
InletSensorStateChange is the generic trap sent for all inlet
sensors. The specific trap for RCM has the object
typeOfSensor set to 27.
Included with the trap are
measurementsInletSensorValue (the residual
current value) and
measurementsInletSensorState (the RCM state that
caused the trap).