Chapter 8: Using the Command Line Interface
499
config:#
sensor inletpole <n> <p> <sensor type> assertionTimeout <as_value>
Variables:
<n> is the number of the inlet whose pole sensors you want to
configure.
<p> is the label of the inlet pole that you want to configure.
Pole
Label
<p>
Current sensor
Voltage sensor
1
L1
L1
L1 - L2
2
L2
L2
L2 - L3
3
L3
L3
L3 - L1
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
voltage Voltage
sensor
activePower Active
power
sensor
apparentPower
Apparent power sensor
powerFactor Power
factor
sensor
activeEnergy
Active energy sensor
unbalancedCurrent
Unbalanced load sensor
Note: If the requested sensor type is not supported, the "Sensor is
not available" message is displayed.
<option> is one of the options:
enable, disable or a numeric value.
Option
Description
enable
Enables the specified threshold for the specified
inlet pole sensor.
disable Disables
the
specified threshold for the specified
inlet pole sensor.
A numeric
value
Sets a value for the specified threshold of the
specified inlet pole sensor and enables this
threshold at the same time.
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...