Power-Sharing Configurations and Restrictions
When either iX7
™
PDU enters the power-sharing mode, BOTH PDUs
involved in the power-sharing connection support "less" external
equipment than usual. It is strongly recommended to remove specific
equipment from both iX7
™
PDUs when making a power-sharing
connection.
Configuration limitations on "both" PDUs:
No USB wireless LAN adapter is connected. That is, you have to
connect both PDUs to a "wired" network if LAN access is wanted.
No asset management strips are connected.
The maximum number of DX environmental packages or door
handles that can be connected decreases. For details, see
Supported Sensor Configurations for Power Sharing
(on page 51).
When either PDU enters the power-sharing mode, you must NOT
physically remove or add environmental sensor packages to BOTH
PDUs.