Chapter 6: Using the Web Interface
164
Load Shedding Mode
When a UPS supplying power to the PX3 switches into battery backup
operation, it may be desirable to switch off non-critical outlets to
conserve UPS battery life. This feature is known as load shedding.
Outlets that are turned off when load shedding is activated are called
non-critical. Outlets that are not affected by load shedding are called
critical outlets. By default, all outlets are critical. To set non-critical ones,
see
Setting Non-Critical Outlets
(on page 163).
When load shedding is activated, the PX3 turns off all non-critical outlets.
When load shedding is deactivated, the PX3 turns back on all non-critical
outlets that were ON before entering the load shedding mode.
Activation of load shedding can be accomplished using the web interface,
SNMP or CLI, or triggered by the contact closure sensors.
Note: It is highly suggested to check the non-critical outlets prior to
manually entering the load shedding mode. The non-critical information
can be retrieved from the Outlets page. See
Outlets
(on page 158) or
Available Data of the Outlets Overview Page
(on page 162).
To enter the load shedding mode:
1.
On the Outlets page, click
> Activate Load Shedding.
2.
Click Activate on the confirmation message.
In the load shedding mode:
The lock icon
appears for all non-critical outlets on the
Outlets page, and you CANNOT turn on any of them.
The message "Load Shedding Active" appears next to the
'Outlets' title.
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...