Chapter 6: Using the Web Interface
163
Next time when power cycling the PX3, it will turn on all outlets based on
the new outlet order.
The new order also applies when performing the power-on or
power-cycling operation on partial outlets.
To set a power-on delay for any outlet:
1.
On the same outlets list, click the 'Delay' column of the outlet that
requires a wait after it is turned on.
2.
Type a new value in seconds.
3.
Click Save.
The PX3 will insert a power-on delay between the configured outlet and
the one following it during the power-on process.
Setting Non-Critical Outlets
Outlets that are turned off when load shedding is activated are called
non-critical. Outlets that are not affected by load shedding are called
critical outlets. See
Load Shedding Mode
(on page 164).
Per default, all outlets are configured as critical.
To determine critical and non-critical outlets:
1.
On the Outlets page, click
> Load Shedding Setup.
2.
To set non-critical outlets, select the checkboxes of those you want.
To select ALL outlets, select the topmost checkbox in the header
row.
3.
To turn non-critical outlets into critical ones, deselect their
checkboxes.
To deselect ALL outlets, deselect the topmost checkbox in the
header row.
4.
Click Save.
Tip: You can also set up non-critical outlet setting by configuring outlets
one by one. See
Individual Outlet Pages
(on page 165).
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...