Chapter 6: Using the Web Interface
323
Field
Data entered
Wait time after successful ping
5
To make the PX3 declare the inaccessibility of the monitored PDU
when that PDU becomes inaccessible for around 12 seconds (4
seconds * 3 pings), enter the following data.
Field
Data entered
Wait time after unsuccessful ping
4
Number of consecutive unsuccessful pings for
failure
3
To make the PX3 stop pinging the target PDU for 60 seconds (1
minute) after the PDU inaccessibility is declared. After 60
seconds, the PX3 will re-ping the target PDU, enter the following
data.
Field
Data entered
Wait time before resuming pinging after
failure
60
The "Number of consecutive failures before disabling feature (0 =
unlimited)" can be set to any value you want.
5.
Click Create.
Step 2: Create an event rule to send SNMP notifications for the
target PDU
1.
Choose Device Settings > Event Rules.
2.
Click
.
3.
Select the Enabled checkbox to enable this new rule.
4.
Configure the following.
Field/setting
Data specified
Rule name
Send SNMP notifications for PDU
(192.168.84.95) inaccessibility
Event
Choose Server Monitoring > 192.168.84.95
> Unreachable
Trigger condition
Select the Unreachable radio button
This will make the PX3 react only when the target PDU becomes
inaccessible.
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...