Chapter 6: Using the Web Interface
147
Field
Function
Note
*Inrush Guard
Delay
Prevents a circuit breaker trip due to
inrush current when many devices
connected to the PDU are turned on.
Range: 100 milliseconds to 2
seconds
See
Inrush Current and Inrush
Guard Delay
(on page 151).
Peripheral Device
Z Coordinate
Format
Determines how to describe the
vertical locations (Z coordinates) of
Raritan environmental sensor
packages.
Options: Rack-Units and
Free-Form
See
Z Coordinate Format
(on page
To specify the location of any
sensor/actuators in the data center,
see
Individual Sensor/Actuator
Pages
(on page 188).
Peripheral Device
Auto Management
Enables or disables the automatic
management feature for Raritan
environmental sensor packages.
The default is to enable it.
See
How the Automatic
Management Function Works
(on
Altitude
Specifies the PX3 device's altitude
above sea level when a Raritan's DPX
differential air pressure sensor is
attached.
Range: 0 to 3000 meters (0 to 9842
feet)
The device's altitude is associated
with the altitude correction factor.
See
Altitude Correction Factors
(on page 684).
The default altitude measurement
unit is meter. See
Setting Default
Measurement Units
(on page
You can have the measurement
unit vary between meter and foot
according to user credentials. See
Setting Your Preferred
Measurement Units
(on page
3.
Click Save.
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...