Chapter 5: Introduction to PDU Components
124
Replaceable Controller
A PX3
Zero U model provides flexibility for replacement of its controller.
The controller, which contains the dot-matrix LCD display and
connection ports, is usually located in the middle of the PDU.
If the controller is broken, you can simply send the controller back to
Raritan for repair, or purchase a new controller from Raritan.
1U / 2U PDUs and all of PX3-3000 series do NOT support this feature.
To request a new controller:
Contact [email protected] to request a new PX3 controller.
Include these details with your request:
The serial number of the PDU
The serial number of the controller board
The full model number of the PDU
The firmware version that the PDU is running (if known).
To replace a controller:
1.
PDU is NOT required to be powered off.
2.
Loosen the screws at two sides of the PX3 controller, and lift it up.
Note: Loosen the screws instead of removing them.