Diagnostics
617
02/16 MN05013001Z EN
In the standard circuit diagram, the contact DG01Q1 indi-
cates with status 1 that he status “Wait for rising edge at
Reset” is present on safety function block ES01.
With DG01Q1 set, you start the appropriate text output via
the text output function block of an easySafety device, or
alternatively via the easyNet to a message text screen
element on an MFD-Titan. The text or message text must
have been created beforehand. The example shows the
Reset message using function block D01.
With the message text screen element you can also use the
status code at output DG..QV (diagnostics register) as a
status value for switching between different message texts.