Commissioning NET stations
537
02/16 MN05013001Z EN
Figure 281: CONFIGURE menu
Requirement for the configuration using NET station 1:
• You must have wired your network as a “loop through”
topology.
• All stations must be correctly connected to the NET and
the termination resistors must have been connected.
• All stations have power, show the basic menu in the
device display (the status display) and are in operating
mode STOP. The POW and NET LEDs must be permanently
lit.
For the configuration, all devices connected on the NET are
assigned their NET ID in the order in which they were entered
in the station list in the STATION menu. Furthermore, all
devices are automatically set with the baud rate and bus
delay time set on NET station 1.
PROTECTION...
SYSTEM...
MENU LANGUAGE
CONFIGURATOR...
NET...
LINK...
Display NET only in STOP
mode
NET
PARAMETERS...
STATIONS...
CONFIGURE
CONFIGURE?
OVERWRITE
IN
PROGRESS.
Fault scenario
with ID conflict.
Fault scenario with
network fault.
ERR: ID CONFLICT
CONFIGURATION
OVERWRITE ?
ERR: TIME OUT