ea
s
yNet network
544
02/16 MN05013001Z EN
Diagnostics
Diagnostic bits ID01 - ID08 provide information on the
presence or absence of NET stations. The state of the
diagnostic bits is defined by the reception of a sign of life
signal that every NET station sends.
The sign of life signal is sent cyclically depending on the
baud rate.
The presence of the configured NET stations is evaluated at
the following time intervalls:
If the sign of life signal of a configured NET station is no
longer received, the diagnostics bit ID01 -ID08 for the
missing NET station is immediately set to 1 for all remaining
stations.
Baud rate
Station must send a
“sign of life”
every ...
Station detects a
missing sign of life
signal from …
[kB]
[ms]
[ms]
1000
60
180
500
60
180
250
120
360
125
240
720
50
600
1800
20
1500
4500
10
3000
9000
Diagnostics
contact
Failure
ID 01
Fault in easyNet station 1
ID 02
Fault in easyNet station 2
…
…
ID 07
Fault in easyNet station 7
ID 08
Fault in easyNet station 8