![Eaton easySafety Manual Download Page 54](http://html1.mh-extra.com/html/eaton/easysafety/easysafety_manual_3958374054.webp)
Installation
50
02/16 MN05013001Z EN
Figure 13:
Connecting outputs, in this case QS 1
The corresponding relay coils are triggered in the standard
circuit diagram or safety circuit diagram via outputs QS1 -
QS4 and QR1. You can use the signal states of the output
relays in the standard circuit diagram or safety circuit
diagram as N/O contacts for further switch conditions.
The relay or transistor outputs are used to switch loads such
as Connecting: Contactors, relays or motors. Prior to
installation observe the technical limit values and data for
the outputs (
section “Technical data”, page 659).
QS1
1
2
QS1
h
Caution!
easySafety may be used in applications up to safety level 3
in continuous operation in accordance with EN 50156 if:
• the time between the functional checks on easySafety
do not exceed six months.
• redundant relay contacts are used for the safety discon-
nection of the fuel supply on furnaces. This can be
achieved by:
– series connection of two QS outputs (ES4P-221-
DR...),
– use of the internal redundant relay output QR1
Summary of Contents for easySafety
Page 1: ...Manual Control relay suitable for safety circuits Safety ES4P 02 16 MN05013001Z EN ...
Page 4: ...2 ...
Page 42: ...38 02 16 MN05013001Z EN ...
Page 80: ...Installation 76 02 16 MN05013001Z EN ...
Page 112: ...108 02 16 MN05013001Z EN ...
Page 606: ...602 02 16 MN05013001Z EN ...