![Eaton easySafety Manual Download Page 379](http://html1.mh-extra.com/html/eaton/easysafety/easysafety_manual_3958374379.webp)
ES, Emergency-stop
375
02/16 MN05013001Z EN
Outputs
The actual value output QV: Indicates the current actual
value of the discrepancy time.
Diagnostics output DG: Provides information the states of
the function block. It is evaluated in the standard circuit
diagram e. g. with the diagnostics function block.
Table 13:
Diagnostics-/-Error codes
Further information on these outputs is provided in section
“Common features”, page 348.
Parameters
Function, parameterisation in the func-
tion block
QV:
Actual value discrepancy time: Time
DG:
Diagnostics: double word
Status number
Plain text
Hexadecimal (0–F)
decimal (0-9)
0000
0000
No Enable.
2001
8193
Enable issued; waiting for first (or only) input.
2002
8194
Waiting for second input.
2003
8195
Waiting for rising edge at Reset.
2004
8196
Waiting for falling edge at Reset.
2005
8197
Only one channel has been opened.
8003
32771
Emergency-Stop not operated (QS = 1).
F001
61441
Error: Discrepancy time expired.
F00B
61451
Error: Reset and inputs operated on function block
startup.
F00E
61454
Error: Only one channel was opened and closed.