SR, shift register
309
02/16 MN05013001Z EN
Figure 147: Shift register SR..: Forwards operation in DW mode
a
Initial situation:
– SR..EN is not activated, the function block is not active.
– SR..D7 contains the value 8, a 0 is contained in the other
register fields.
b
Transfer of value:
– SR..EN is activated, the function block is active.
– SR..I1 has the value 10.
– With the forwards pulse from SR..FP the register field SR..D1
shifts the content of all register fields one place forwards and
accepts the 10 from SR..I1.
c
Transfer of value:
– SR..EN is activated, the function block is active.
– SR..I1 has the value 52.
– with the forwards pulse from SR..FP the register field SR..D1
shifts the content of all register fields one place forwards and
accepts the 52 from SR..I1.
d
Reset of the register:
– SR..EN is activated, the function block is active.
– Activating SR..RE clears the content of the register.
D1:
D2:
D3:
D4:
D5:
D6:
D7:
D8:
8
0
0
0
0
0
0
0
0
52
10
0
0
0
0
0
0
10
0
0
0
0
0
0
8
0
0
0
0
0
0
8
0
a
b
c
d
SR...DW
Shift Register
EN
SR...DW
Shift Register
EN
RE
FP
>I1
RE
FP
>I1
SR...DW
Shift Register
EN
RE
FP
>I1
SR...DW
Shift Register
EN
RE
FP
>I1
10
1
52
1
1
1
0
D1:
D2:
D3:
D4:
D5:
D6:
D7:
D8:
D1:
D2:
D3:
D4:
D5:
D6:
D7:
D8:
D1:
D2:
D3:
D4:
D5:
D6:
D7:
D8: