background image

Installation and Wiring

1.

Mount the appropriate 8 pin octal socket in a suitable enclosure.  

NOTE: a 600V-rated socket such as the Macromatic 70169-D or

Custom Connector OT08-PC must be used with these products on applications greater than 300V.  When making connections
to the socket, make sure to match the terminal numbers on the socket to the ones shown on the wiring diagram (the wiring
diagram on the relay is the view looking towards the bottom of the relay vs. the top of the socket).

  Use one or two #12-22 solid

or stranded copper or copper-clad aluminum conductors with terminals on the above Macromatic or Custom Connector sockets—a
terminal tightening torque of 12 in-lbs should be used.

2.

Set the VOLTAGE LINE-LINE knob to the actual three-phase line-to-line voltage.  The
Voltage Line-Line knob on the PMPU & the PMPU-FA8 has two ranges (see right): 190-
250V on the low voltage scale and 380-500V on the high voltage scale.  The unit auto
senses the three-phase line-line voltage when applied and automatically selects one of
the two ranges.  The PMP120 has a single adjustable range of 102-138V and the PMP575
has a single adjustable range of 460-600V.

3.

(

For PMPU-FA8, skip to Step 4

)  Set initial settings on the UNDERVOLTAGE TRIP, TRIP

DELAY and RESTART DELAY knobs to minimum.  Set initial setting on the UNBALANCE
knob to maximum.

4.

Connect the three-phase line-line voltage to terminals 3, 4 and 5 (see W iring Diagram on
the side of the relay or on the back of this sheet).   A connection to the neutral or ground
is not required in Wye systems.  DO NOT connect output wires to terminals 1, 2 and 8
until later (Step 13).

5.

RESET: As standard, the PMP Series relays are in the Automatic Reset mode, which means they will automatically reset once the fault has
been corrected.  However, they can be set up in the Manual Reset mode by connecting an external N.C. switch across terminals 6 and 7.
Upon application of three-phase voltage, the PMP Series will go into Manual Reset mode if it recognizes a closure across terminals 6 and
7.  After a fault clears, the relay will not reset until the N.C. switch is opened.  

NOTE:

 this unit can only be set back to Automatic Reset

mode from Manual Reset mode by removing three-phase voltage, removing the N.C. switch across terminals 6 and 7, and reapplying the
three-phase voltage.

6.

Plug the three-phase monitor relay into the socket, making sure the key on the center post is in the
proper orientation before insertion.  

If the relay must be removed from the socket, do NOT rock

the relay back and forth excessively—the center post could be damaged.

7.

Apply three-phase voltage.  The LED indicator should initially flash GREEN if in the Automatic Reset
mode while the relay goes through its start-up delay or waiting for an external switch to be operated
if in the Manual Reset mode and then illuminate solid GREEN.  If the LED turns RED solid or
flashing, a fault condition exists and must be corrected.  

Use the LED Status Table at right or the

Troubleshooting Guide on back to determine exact cause of fault.

  Make required corrections.

Settings

8.

REMOVE THREE-PHASE VOLTAGE for Steps 9-13.  (

For PMPU-FA8, REMOVE THREE-PHASE VOLTAGE and skip to Step 13

)

9.

Set the RESTART DELAY knob.  This setting should be the time period required after a fault has been cleared before the relay should
automatically energize.  NOTE: this value is ignored when in the Manual Reset mode (see Step 5).

10. Set the UNDERVOLTAGE TRIP knob between 80 and 95% of the line-line voltage setting.  This value should be the same as the minimum

operating voltage for the equipment to be adequately protected.

11. Set the TRIP DELAY knob.  This is the maximum time period that an unbalance, undervoltage or overvoltage condition should be allowed to

last.  Too short a setting will cause nuisance tripping if there are momentary changes in the three-phase voltage.  Too long a setting could
cause damage to the equipment.  Note that the setting should be at least slightly longer than the time a three-phase motor is drawing its
inrush or startup current.  This will avoid nuisance tripping caused by the starting current.

12. Set the UNBALANCE knob.  This setting should be the maximum allowable unbalance in phase voltage that the three-phase system can

tolerate. Too low of a setting can cause nuisance tripping.  Too high of a setting may not adequately protect the system.

(Continued on Back)

INSTALLATION

 

INSTRUCTIONS

PMP S

ERIES

T

HREE

-P

HASE

 M

ONITOR

  R

ELAYS

901-0000-140

April, 2014 

(Replaces November, 2008)

DANGER!

Potentially hazardous voltages are present.  Electrical shock can cause death or serious injury.

Installation should be done by qualified personnel following all National, State & Local Codes.

BE SURE TO REMOVE ALL POWER SUPPLYING THIS EQUIPMENT BEFORE CONNECTING OR DISCONNECTING WIRING.

READ INSTRUCTIONS BEFORE INSTALLING OR OPERATING THIS DEVICE.  KEEP FOR FUTURE REFERENCE.

IMPORTANT: READ THIS FIRST IF REPLACING A PMP SERIES PRODUCT WITH DATE CODE OF 1414 OR EARLIER

Macromatic made several product design enhancements on all PMP Series products manufactured with Date Code of 1415 or later (2nd week of April
2014). These include a dial-in-dial line-line voltage scale on the PMPU with an increased 190-500V range, new LED fault codes & the ability to set the Line-
Line Voltage with power applied. Basic functionality & protection has been retained.

PMPU-FA8

190-500V

PMPU

190-500V

Reviews: