SE, Start element
461
02/16 MN05013001Z EN
Further information on this output is provided in section
“Common features”, page 348.
Coils and contacts
Function block coils initiate the functions of the function
block and monitor the connected safety transmitters.
The contacts of a safety function block confirm the enable
conditions present, selected operating modes or indicate
errors.
Coils
You close the function block coil SE..I1 directly at the device
terminals IS1 to IS14 or associate it with any combination of
contacts and connections. The coil initiates the safe start
command in the safety circuit diagram.
The actual Start command is triggered via the Reset coil
SE..RE. If you have set MST (Manual Start), the coil responds
to the rising edge. If you have selected CST (Controlled
Start), the coil responds to the falling edge. Use the coils only
in the safety circuit diagram.
The function of the function block is enabled either in the
safety or in the standard circuit diagram with its enable coil
SE..EN.
Status number
Plain text
Hexadecimal (0–F)
decimal (0-9)
0000
0000
No Enable.
2001
8193
Enable issued; waiting for input.
2003
8195
Waiting for rising edge at Reset.
2004
8196
Waiting for falling edge at Reset.
8008
32776
Start signal triggered (QS = 1).
F00B
61451
Error: Reset operated on function block startup.