Safety function blocks
386
02/16 MN05013001Z EN
Enable time
When activated you can define a maximum permissible
enable time for bridging the guard.
This parameter is factory set to OFF. This means that no
maximum permissible enable time is required.
Outputs
Actual value output QV: Indicates the current actual value of
the enable time.
Diagnostics output DG: Provides information the states of
the function block. It is evaluated in the standard circuit
diagram e. g. with the diagnostics function block.
Parameters
Function, parameterisation in the func-
tion block
>ED
OFF; 0.5 - 10.0 min; adjustable in increments of
g
0.5 min.
Parameters
Function, parameterisation in the func-
tion block
QV:
Actual enable time: Time
DG:
Diagnostics: double word