BT, data block transfer
201
02/16 MN05013001Z EN
Example 1:
Initialising marker blocks, direct definition
marker ranges
The value of marker byte 10 is to be transferred to marker
bytes 20 to 29.
• Parameters of function block BT01:
– Source range:
>I1 MB10
– Destination range: >I2 MB20
– Number of bytes:
>NO 10
After a rising edge from 0 to 1 at coil BT01T_ the value 123
is present in the marker bytes MB20 to MB29.
Source-
range
Value of
source
marker range
(decimal)
Destina-
tion
range
Value of
destination
marker
range
(decimal)
MB10
123
MB20
123
MB21
123
MB22
123
MB23
123
MB24
123
MB25
123
MB26
123
MB27
123
MB28
123
MB29
123