Safety function blocks
498
02/16 MN05013001Z EN
Outputs
Actual value output QV: indicates the currently elapsed time.
Diagnostics output DG: Provides information the states of
the function block. It is evaluated in the standard circuit
diagram e. g. with the diagnostics function block.
Table 22:
Diagnostics-/-Error codes
Further information on these outputs is provided in section
“Common features”, page 348.
Parameters
Function, parameterisation in the func-
tion block
QV:
Actual elapsed time value: Time
DG:
Diagnostics: double word
Status number
Plain text
Hexadecimal (0–F)
decimal (0-9)
0000
0000
No Enable.
2001
8193
Enable issued; waiting for start via input TS..TR.
200B
8203
Waiting for decreasing trigger signal; output not active.
200C
8204
Allocated time running, output not active.
200D
8205
Allocated time stopped, output not active.
800C
32780
Timing relay output is active (QS = 1).
800D
32781
Waiting for decreasing trigger signal; output active (QS = 1).
800E
32782
Allocated time running, output is active (QS = 1).
800F
32783
Allocated time stopped, output is active (QS = 1 ).