Commissioning NET stations
541
02/16 MN05013001Z EN
h
Caution!
Operating the NET with two masters (two stations with
NET-ID 1) is not allowed, and leads to malfunctions on the
NET.
Possible effects of this type of incorrect configuration with
two masters competing against each other, and in which
one is operated in the STOP operating mode and the other
in the RUN operating mode, are as follows:
NET stations with NET-ID 2 - 8 that should follow the
operating mode changes of the NET station with NET-ID 1
automatically during operation (REMOTE RUN parameter
definition) keep toggling constantly between the STOP
and RUN operating modes.
When integrating a master that is already configured into
an existing NET, please make sure that there is no other
station with NET-ID 1 on the NET.
Also, when performing the configuration from easySoft-
Pro or easySoft-Safety and a local connection to a station,
please make sure you do not assign NET-ID 1 to this
station if there is a master on the NET already.
Tip: Carry out a NET configuration through NET station 1
after every change to the NET.